www.fieldcontrols.comPlease retain these instructions after installation.This device MUST be installed by a qualified agency in accordance with the manu
page 10PV SERIES POWER VENTER: VERTICAL VENTING OPTIONDiagramDillustratescorrectandincorrectinstallationofPVseriesventerinverticalventco
page 11REPLACEMENT PARTS LISTDESCRIPTION PVO-300 PVO-600Motor 46032000 46083300Blower Wheel 46033400 46089400Post Purge Relay Timer 46144700 46144700P
Phone:252.522.3031•Fax:252.522.0214www.fieldcontrols.comLIMITED WARRANTYField Controls, LLC (“Company”) warrants that its products shall be free f
page 2Figure 1UNIT SPECIFICATIONS (See Table 1 and Figure 1)SIDEWALL VENT HOODS (Model SWH-1)Theventhoodshouldbechosenthatmatchestheoutletsi
page 3Example:4"to8"reducer,thereducerratioisd/D=4⁄8=1⁄2. To estimate the equivalent foot length for thetting,usethesmalle
page4INSTALLATION SAFETY INSTRUCTIONSCAUTION: This device must be installed by a qualified installer in accordance with the manufacturer's instal
page5CONNECTING VENTER TO APPLIANCETheventingsystemshouldbeinstalledandsupportedinaccordancewiththeNationalFuelGasCodeANSIZ233.1,or
page 6Diagram CDiagram B
page 7MULTIPLE APPLIANCE SYSTEMSWhenusingonePVOpowerventertocommonvent more than one appliance, a Control Kit is required for each additional
page8 Figure 6Figure 7 Figure 8PRESSURE SWITCH ADJUSTMENTWiththeventerairowsetandthe1. appliance operating at the best operating efficiency,
page 9GENERAL INSTALLATION INSPECTIONFollow recommended procedures for safety inspection of a heating appliance in accordance with the NationalFuelG